P3APS19001EN IEC 61850 Configuration Instructions

7.2. Creating an SCL file offline

1. To create the setting file template:

a. Click the icon on the top left corner in Easergy Pro.

b. From the drop-down menu that opens, select New.

c. In the Create configuration window that opens, carefully select the

settings according to the device ordered.

IEC 61850 configuration instructions

7. Exporting SCL files

28

P3APS19001EN




Figure 24 - Creating a configuration

2. Create the SCL file as instructed in 



Creating an SCL file

.

7. Exporting SCL files



IEC 61850 configuration instructions

P3APS19001EN

29



8. Appendix: Blocking example

Number of GOOSE to subscribe to:

Each P3 can subscribe up to 64 APPID (publishers) from up to five MAC



addresses

Maximum number of GOOSE messages to be processed at the same time:



each GOOSE control block (GCB) or APP ID is processed typically in 7 ms

(minimum is 3.5 and maximum 10 ms).

Typical blocking scheme on a busbar:



Because each GOOSE sent from any feeder has the same function

(blocking the subscriber overcurrent protection), the blocking happens

upon the reception of the first GOOSE received.

For example, if there are 32 feeders:



Fault on any line: A single GOOSE is sent by the device seeing the

fault.



This GOOSE is processes by the incomer device, typically in 7 ms



(min. 3.5 ms and max. 10 ms).

Figure 25 - Typical blocking scheme