P3APS19001EN IEC 61850 Configuration Instructions

data configuration setting view.

Bit index

For binary GOOSE. Select the right bit out of possible stream. 0

is the first bit (if set to 1, it reads the second bit).

Value

Not a setting but showing actual value when connected.



VAI Unit

For analog GOOSE. Preconfigured. Select the unit of the value

sent by the GOOSE.

Status


Not a setting but showing actual status when connected.

Initial value

For binary GOOSE. Preconfigured to "Last". "Initial" means after

power on or when Ethernet connection is lost.

Set the value according to the requested application

"Last" means last value received is memorized



"Off" means = "0"

"On" means ="1"



In use

Select the In use checkbox for N1.

Supervision group Preconfigured to Group1.

When the GOOSE status is other than "OK", the Global



Supervision group alarm is always raised.

When the GOOSE status is other than "OK", the selected



Supervision group alarm is raised (information to be used in

the Matrix or Logic)



NOTE: The subscruber configuration setting view is slightly different for

analog and binary GOOSE.

Figure 17 - Analog GOOSE subscriber data points

4. GOOSE communication configuration

IEC 61850 configuration instructions

P3APS19001EN

23



Figure 18 - Binary GOOSE subscriber data points

IEC 61850 configuration instructions

4. GOOSE communication configuration

24

P3APS19001EN