P3APS19001EN IEC 61850 Configuration Instructions

NOTE: Do not select Structure if Include Quality in GOOSE

dataset is selected.

NOTE: The maximum number of P3 subscribers is 64 but the

quality bits is not processed by P3.



NOTE: Only signals used and set in “data map” shall be listed

here. The GOOSE message is sent only when all the listed signals

are set and in OK status. It is mandatory to select “None” for non-

selected data.

5. In the Communication > IEC 61850 measurement config > Deadband

values setting view:

To send values, even if the threshold is not reached, select an integration



time of the current.

The integration time is the quickest time a small new value (but below the

threshold) can be sent. The longer the integration time, the smaller is the

integrated step change needed.

Figure 15 - Deadband integration time

4. GOOSE communication configuration