P3APS19001EN IEC 61850 Configuration Instructions

DI for test mode: selection of digital inputs that can be used to put the

GCB to test mode. A digital input needs to be configured here. The test bit

follows the status of this set digital input.



Test mode: select the checkbox to enable test mode.



Application ID: update the value according to the subscriber’s

configuration.

NOTE: The rest of the parameters in this setting view are pre-configured

and shall only be changed by experts.

4. GOOSE communication configuration

IEC 61850 configuration instructions

P3APS19001EN

19



Figure 12 - GOOSE configuration

3. In Communication > IEC 61850 data map(x), select the In use checkbox for

logical nodes (LN) that contain the data to be published.

For example, if IL1 is published, select In use for I3pMMXU1.

Browse through all the IEC 61850 data map(x) views until you find the right

line.


Figure 13 - IEC 61850 data map(4)

IEC 61850 configuration instructions

4. GOOSE communication configuration

20

P3APS19001EN




4. In the Communication > GOOSE GCB1: data points > DSG1 Data

configuration setting view, define the following settings:

In the Signal column, select the data to be published, for example IL1.