2. IEC 61850 introduction
The IEC 61850 protocol is available with the optional inbuilt Ethernet port. The
IEC 61850 protocol can be used to read/write static data from the device or to
receive events and to receive/send GOOSE messages from/to other devices.
The IEC 61850 server interface supports the following features:
•
configurable data model: selection of logical nodes corresponding to active
application functions
•
configurable pre-defined data sets
•
dynamic data sets created by clients
•
reporting function with buffered and unbuffered report control blocks
•
control model: direct with normal security and with enhanced security, SBO
with normal and with enhanced security
•
horizontal communication with GOOSE: configurable GOOSE publisher data
sets, configurable filters for GOOSE subscriber inputs, GOOSE inputs
available in the application logic and output matrix
•
32 data points can be published with GOOSE (two goose control blocks with
maximum 16 data points).
•
64 binary data points and five analog data points can be subscribed in
GOOSE (maximum five different MAC addresses).
•
The maximum number of clients is eight (the maximum number of BRCBs is
eight and the maximum number or URCBs is eight).
•
Both Edition 1 and Edition 2 are supported and can be selected with a
parameter.
The inbuilt Ethernet is available as a communication option. For more information,
see the manuals of the individual devices.
2. IEC 61850 introduction
IEC 61850 configuration instructions
P3APS19001EN
5