P3APS19001EN IEC 61850 Configuration Instructions

3.5. Generic events

You can also configure so-called generic events to map any application events of

the device to maximum eight indication data objects of the EvtGGIO183 logical

node of the IEC 61850 interface. The status of the indication data object is

determined by ON and OFF events set for the corresponding index in the table.

NOTE: If only an "ON event" is defined for an indication, the transition to OFF

state is generated automatically after reporting the ON state (momentary ON

state). And the same applies if only an "OFF event" is defined for an indication

(momentary OFF state).