90225-1.30 Instruction Manual CT-T1

8.1 Main Screen
The selection of the CT under test’s 
windings that are to be measured are 
selected in the Main screen. The grid can 
directly be used to select the windings.
Figure 17: CT-T1 operation menu structure
90225-1.30 Instruction Manual CT-T1
Page 34 of 62


Additionally the Xn buttons can be used to 
select all windings with the given tap. For 
example if you want to measure the 
windings X3-X4 and X3-X5 you can press 
X3 on the top.
The symbols used to either select all 
windings or all adjacent windings.
The designation can be unselected if all 
associated windings are marked. A button 
press for a certain grouping with at least 
one untagged winding marks all and a 
second press clears the selection.
In order to delete individual measurement 
data select the desired measurement data 
to be deleted and press 
[x]
.
Another window would appears. Press 
Yes to confirm or No to abort. 
90225-1.30 Instruction Manual CT-T1
Page 35 of 62


8.2 Profile
The Info screen is divided into the following four tabs:
"Rated Current"
The rating for the windings from CT 
nameplate can be entered in this form. 
These values are used to determine the 
turns ratio errors.
"Name Plate" 
The name, serial number (S/N), type, 
manufacturer, location of the CT under test 
along with remarks can be stored here.
"Limits" 
To protect the CT under test, Voltage and 
Current limits can be set here. Also 
maximum acceptable ratio error can be 
entered here.
"Actual Result"
The date, time, device name, and the serial
number of the CTT1 are listed in this page.
90225-1.30 Instruction Manual CT-T1
Page 36 of 62


8.3 Measuring
Press the Start button to perform the knee
point and turns ratio measurements in a 
completely autonomous fashion 
successively for each selected winding. 
The measurement can be adjusted in the 
Setup screen. Please see Section 8.6, for 
more details. The name plate of the CT 
under test and its characteristics can be 
entered prior to the measurement on the 
Info screen.
The user simply has to press the Surveillance switch during the automatic measurement process. 
The red area marks the hazardous output voltage that could harm persons. To ensure the user is 
aware of the situation, the Surveillance switch needs to be pressed and hold on while the output 
voltage is above the limit. The red area would disappears when the surveilance swith is pressed.
The progress is displayed on the screen while each winding is measured. The live view contains a 
large square log-log graph on the left. The output voltage and current are marked with the cross 
and are listed on the right as well. During the Excitation process the curve is drawn as a bold line. 
The previously recorded curves are displayed as thin lines.
The winding tap under the test is displayed 
on the top right corner along with the 
measurement steps (Degauss, Excitation 
and Turns ratio). The background of this 
field changed according to the potential 
risk. The background is red during the 
Degauss process and is orange during the 
Excitation and Turns ratio processes.
To abort the measurement press Stop or 
press the Emergency switch. If the 
Surveillance switch is released while the 
output voltage is harmful, the measurement
stops as well.