Easergy P3 iec 61850 configuration instructions Application Book P3aps19001en publication Date 03/2019


Configuring a device to publish a binary GOOSE message



tải về 3.09 Mb.
Chế độ xem pdf
trang11/26
Chuyển đổi dữ liệu27.02.2022
Kích3.09 Mb.
#51013
1   ...   7   8   9   10   11   12   13   14   ...   26
P3APS19001EN IEC 61850 Configuration Instructions

4.1. Configuring a device to publish a binary GOOSE message

Before starting this procedure, configure the redundancy protocol for Ethernet

(PRP or RSPT) as instructed in 

3.8. Configuring the redundancy protocol for

Ethernet

 on page 13.

IEC 61850 configuration instructions

4. GOOSE communication configuration

16

P3APS19001EN




1. If GOOSE messages are to be used for protection purposes, in the

Communication > GOOSE configuration > Publisher parameters setting

view, set Max retransmission timeout to 5 s.

2. In the Communication > GOOSE configuration > Publisher configuration

GCB 1 setting view, set the GOOSE configuration as follows:



Enable: select the checkbox.



GOOSE ID: type a name that matches the subscriber’s configuration.