ANSI-TIA Standards
8718 source
TECHNICAL
Call 1-800-626-0005
www.hubbell-premise.com
N17
568-B.2-10 Category 6A
ANSI/TIA-568-C.2: Category 6A UTP Cabling
Augmented Category 6, or Category 6A unshielded twisted pair (UTP) cable is designed to support 10GBASE-T (10 Gigabit Ethernet) 
transmission in accordance with IEEE802.3an requirements. IEEE802.3an was officially ratified in June 2006. The 568B.2-10 
standard for Category 6A was officially ratified in February 2008.
X
Category 6A permanent link and channel performance are defined to 500 MHz.
X
Alien Cross Talk (AXT) parameters are defined to 500 MHz.
X
AXT is a measure of signal coupling from energized pairs in a disturber cable or component into disturbed pairs within 
surrounding cables or components.
X
Category 6A AXT parameters are summarized below (see Glossary also):
• 
ANEXT (Alien Near End Crosstalk).
• PSANEXT (Power Sum Alien Near-End Crosstalk).
• AACRF (Attenuation to Alien Crosstalk Ratio, Far End). NOTE: Previously referred to as AFEXT.
• PSAACRF (Power Sum Attenuation to Alien Crosstalk ratio, Far-End). NOTE: Previously referred to as PSAFEXT.
To mitigate the effects of AXT, the cable design shall meet the “worst case” 6-around-1 AXT requirements as shown below. Larger wire 
size, tighter twisting and thicker cable jacket are key design parameters. As a result, the cable diameter is larger, and will have an 
impact on installation practices. Refer to Hubbell’s “10 GbE Cabling Guidelines for more details.
X
Field-testing of AXT in installed links or channels is optional per 568B-2-10.
X
AXT field testing equipment is identified in the table on page N13.
X
Link and channel components must also be designed to mitigate AXT.
TIA/TSB-155: Field AXT Mitigation for Installed Category 6 Cabling
Telecommunications Systems Bulletin TSB-155, released in March 2007, was developed to qualify installed Category 6 cabling for 
operation at 500 MHz to support 10GbE transmission. Category 6 cabling used for 10GbE applications is restricted to the 
performance level of the cable and the AXT environment.
X
Defines field AXT test parameters for installed Category 6 cabling links.
X
Establishes length restrictions for installed Category 6 cabling.
X
Standard Category 6 cabling: 37 meters maximum (no testing).
X
Standard Category 6 cabling: 37 to 55 meters maximum (AXT testing recommended, mitigation not likely).
X
Enhanced Category 6 cabling: > 55 meters (Mitigation and AXT testing highly recommended, , mitigation expected).
X
NOTE: The primary limitation with 10GbE operation is ANEXT. Individual Cat 6 links with no EMI should be able to support
10GbE up to 100m. Multiple links in parallel become a concern with ANEXT.
The mitigation procedure suggested by TSB-155 is outlined below. Each mitigation step requires field AXT testing to 500 MHz for 
verification.
X
Unbundle cables and patch cords.
X
Substitute ScTP patch cords and equipment cords.
X
Substitute Category 6A jacks.
X
Substitute Category 6A panels.
"Worst Case" 6 around 1 AXT Test Configuration.