22
|
ni.com
|
NI USB-6001/6002/6003 User Guide
Source/Sink Information
When used in output mode, the default configuration of the digital ports is active drive, allowing
3.3 V operation with a source/sink current limit of ±4 mA.
The ports can be configured as open collector using the NI-DAQmx API, allowing operation
with a different voltage level when used in conjunction with an external user-provided pull-up
resistor. Figure 14 shows an example of this connection.