3BSE035983-510 - en AC 800M 5.1 OPC Server

OPC Alarm and Event Server
The OPC Alarm and Event Server generates a stream of information, mostly event 
notifications, and distributes them to the Alarm and Event clients. OPC Alarm and 
Event 1.02 standard is supported. For more information, see 
Section 5, Alarm and 
Event
.
When running with a third part OPC client in an 800xA, it is important to only 
connect to the 800xA System OPC interface. Thus you must not connect to the 
OPC Server for AC 800M. It is only the 800xA System OPC interface that is 
adequate enough to handle security issues, band width, performances etc in this 
type of 800xA configurations with a third part client.


System Configuration
Section 1 Introduction
14
3BSE035983-510
 
Figure 1. OPC Server configuration in a system.
System Configuration
The following basic rules apply to system configuration and OPC servers:

One OPC server can receive data or event notifications from multiple control 
systems,

A maximum of three OPC servers are allowed to subscribe to Data Access 
and/or Alarm and Event from one controller,

A control system can send data or event notifications to multiple subscribing 
OPC servers,

Multiple OPC clients can subscribe to data or event notifications from the same 
OPC server.

A maximum of five third-party OPC clients are allowed to subscribe to Data 
Access and/or Alarm and Event from one OPC server,
Controller
OPC Server for 
AC 800M
Control 
Builder
Controller
Ethernet
Controller
OPC Client
MMS server
COM/DCOM
MMS


Section 1 Introduction
Network Considerations
3BSE035983-510
15
 

A maximum of four Ethernet links (two redundant) are supported via Ethernet 
cards.

A third-party OPC client should, if possible, be installed on the same PC as the 
OPC server. Otherwise, there is a potential risk that communication will not 
restart after a communication failure (only for CCB Users).
For details regarding the maximum number of supported controllers from which the 
OPC server subscribes data, refer to Compact Control Builder AC 800M Product 
Guide (3BSE041586*).