System Configuration
Section 1 Introduction
14
3BSE035983-510
Figure 1. OPC Server configuration in a system.
System Configuration
The following basic rules apply to system configuration and OPC servers:
•
One OPC server can receive data or event notifications from multiple control
systems,
•
A maximum of three OPC servers are allowed to subscribe to Data Access
and/or Alarm and Event from one controller,
•
A control system can send data or event notifications to
multiple subscribing
OPC servers,
•
Multiple OPC clients can subscribe to data or event notifications from the same
OPC server.
•
A maximum of five third-party OPC clients are allowed to subscribe to Data
Access and/or Alarm and Event from one OPC server,
Controller
OPC
Server for
AC 800M
Control
Builder
Controller
Ethernet
Controller
OPC Client
MMS server
COM/DCOM
MMS
Section 1 Introduction
Network Considerations
3BSE035983-510
15
•
A maximum of four Ethernet links (two redundant)
are supported via Ethernet
cards.
•
A third-party OPC client should, if possible, be installed on the same PC as the
OPC server. Otherwise, there is a potential risk that
communication will not
restart after a communication failure (only for CCB Users).
For details regarding the maximum number of supported controllers from which the
OPC server subscribes data, refer to
Compact Control Builder AC 800M Product
Guide (3BSE041586*).