Isometer® iso685-d-p iso685W-d-p iso685-s-p iso685w-s-p insulation Monitoring Device with integrated locating current injector for it ac systems with galvanically connected rectifiers and inverters and for it dc systems



tải về 5.18 Mb.
Chế độ xem pdf
trang22/75
Chuyển đổi dữ liệu22.08.2023
Kích5.18 Mb.
#55079
1   ...   18   19   20   21   22   23   24   25   ...   75
iso685-D-P D00170 M XXEN

WARNING
L1
L2
PE
U
n
U
S


Connection
Connection
iso685-D-P_D00170_03_M_XXEN/07.2017
24
6.4 Connection to a DC system
Position the terminal cover and click it into place
For systems > 690 V and with overvoltage category III a fuse for 
the connection to the system to be monitored must be provided. 
Recommendation: 2 A fuses.
Risk of injury, fire and damage to property due to a short circuit! 
According to DIN VDE 0100-430, devices used to protect against a short
circuit when terminals L1/+, L2 und L3/- are coupled to the IT system to be
monitored can be omitted if the wiring is carried out in such a manner as
to reduce the risk of a short circuit to a minimum. Ensure short-circuit-
proof and earth-fault-proof wiring.
WARNING
L+
L-
PE
U
S
U
n
6.5 Connection to the X1 interface
Position the terminal cover and click it into place
I1
I2
I3
A
B
M+
Q2
Q1
+
Electrical overload protection. 
Auto shut-off in the event of a short 
circuit and transients (resettable)
Input 1
Input 2
Input 3
RS-485 A
RS-485 B
Ground
Analogue output
Output 2
Output 1
+24 V


Connection
Connection
iso685-D-P_D00170_03_M_XXEN/07.2017
25
6.6 Connection to the supply voltage
External Power supply for powering the ISOMETER® via terminal X1 must
fulfil immunity and emission standards of the required application. For
wiring longer than 1 m the use of a shielded cable is prescribed.