Connection
iso685-D-P_D00170_03_M_XXEN/07.2017
31
6.11.4 Connection to a DC system
For systems > 690 V and with overvoltage category III a fuse for the connection to the system to be monitored must be provided.
Recommendation: 2A screw fuses.
BS-Bus
IT-System
O
K
R(an) 40kΩ/10kΩ
O
K
>20
MΩ
>20
MΩ
L+
L-
PE
U
S
U
n
to the loads
to the loads
A1/+ A2/-
L1/+
L3/-
L2
KE E
X1
ISOSCAN®
EDS440
I
L
7 6
5
3
8
4
2
0
1
6
5
3
4
2
0
1
9
8
EDS440
ISOSCAN®
TEST
MUTE
RESET
ALARM
ALARM
ON
COM
SERVICE
CHANNELS
SLAVE ADDRESS
12
11
10
9
8
7
1
2
3
4
5
6
1
7
I
L
I
n
I
∆
L
I
∆
n
l l
X1
A1/+ A2/-
l
k
1 2 3 4 5 6 7 8 9 10 11 12
13 14
23 24
X1
U
S
A1 A2
PGH ON
iso685-D-P_D00170_03_M_XXEN/07.2017
33
Commissioning
7. Commissioning
7.1 General initial commissioning process
1. Check that the ISOMETER® is properly connected to the system to be monitored.
2. Connect the supply voltage to the ISOMETER®. Adjust the device using the commis-
sioning wizard. Afterwards, the ISOMETER® performs a self test in four steps. The
alarm relays are not checked during this test. After completion of the test, the meas-
ured insulation resistance is shown on the display. If the value exceeds the response
values indicated in the lowest line of the display, the message "OK" will additionally
be displayed.
3. Check the ISOMETER® in the system being monitored, e.g. using a suitable resistance
to earth.
After setting the response value
R
an2
for alarm 2, the device starts a self test, makes the
first measurement and outputs the measured insulation resistance values of the IT sys-
tem being monitored, then commissioning is completed.
For customer-specific configured devices, the commissioning wizard
might be deactivated and cannot be run. In this case, the device is preset.
However, the commissioning wizard can be started as described at
“Recommissioning” on page 35
.
Observe device status!
The device is in an alarm state until initial commissioning has been
completed.
Commissioning flow chart
Commissioning the ISOMETER
®
Adjust basic settings if
necessary
Control and/or connect the EDS
to the ISOMETER
®
:
* EDS44…-L: use BS bus
* EDS44…-S: use BB-Bus
Make any other necessary
settings for the EDS44… in the
ISOMETER
®
menu:
EDS
Set the maximum locating current
in the ISOMETER
®
menu:
EDS General Current
* EDS440…: 10…50 mA
* EDS441…: 1…5 mA
Install
the device according to the
wiring diagram
and documentation
Connect the supply voltage
Connect the system voltage
The ISOMETER
®
performs a self
test
Function test with a suitable
resistance between system and
earth. Resistance value: 50% of
the response value Alarm 2
Remove
the resistance
The ISOMETER
®
is properly
connected and
functions reliably
Commissioning the EDS44…
Function test with a suitable
resistance between system and
earth. Resistance value: 50% of
the response value Alarm 2
Remove the resistance
The ISOMETER
®
and EDS44...
combination is properly connected
and functions reliably
Set BS address = 1 (Master)
System commissioning of
ISOMETER
®
with EDS44…
Install the device according to the
wiring diagram and documentation
Connect the supply voltage
Delete the alarm messages as
described in the device
documentation
The EDS44… is properly
connected and ready for operation
Disconnect supply voltage
of
all devices
Connect the supply voltage
to all devices
Search for adjustable measuring
channels in the ISOMETER
®
menu:
EDS Scan for channels
Activate measuring channels in
ISOMETER
®
menu:
EDS Enable channel
Run the commissioning
wizard
The
ON LED flashes until the
device is ready for use
Set EDS mode in the ISOMETER
®
menu: EDS General
Mode
EDS44…-L:
Set the BS adress using
the
rotary switches on the EDS
For further information regarding de-
vice settings, refer to chapter
“Settings”
from page 46
.
Commissioning
Commissioning
iso685-D-P_D00170_03_M_XXEN/07.2017
34
7.2 Initial commissioning
Follow the instructions of the commissioning wizard on the display.
7.2.1 Set language
The language selected here will be used in the menu and for device messages.
7.2.2 Set time and date
Alarm messages in the history memory and the insulation resistance value over time can
only be assigned correctly to the isoGraph when the date and time are set correctly.
Check network function!
When the device has been integrated into a network, the influence on the
network has to be checked with the device switched on and off.
Language
6.6.2
• Deutsch
o English
o ...
6.6.4
14.01.2014
31
Date
min.
1
max.
31
lle
Commissioning 6.6
2/9
Please set the
current date
and time.
7.2.3 Setting system type
By setting the system type the insulation monitoring device can be optimally adapted to
the system to be monitored. The system type is essential information for the insulation
monitoring device in order to determine the insulation resistance correctly.
7.2.4 Set profile
In order to optimally adapt the insulation monitoring device to the system to be moni-
tored, select a profile here that suits your system. For an overview of the profiles refer to
“Device profiles” on page 74
. The profile "Power circuits" is suitable for most IT systems.
7.2.5 Setting EDS mode
Set the mode for the insulation fault location to manual, automatic or 1 cycle.
For further information, refer to
“Mode” on page 54
.
6.6.6
• DC
o AC
o 3AC
System type
lle
6.6
5/11
Commissioning
Please
choose the
type of system
that best suits
your installation.
6.6.7
Profile
• Power circuits
o Control circuits
o Generator
o High capacitance
o Inverter>10 Hz
o Inverter<10 Hz
lle
6.6
6/11
Commissioning
Please select a
profile that suits
your application.
Mode
•
manual
o
auto
o
1 cycle
6.6.8
lle
Commissioning 6.6
Please select the
EDS mode.
7/11
Commissioning
Commissioning
iso685-D-P_D00170_03_M_XXEN/07.2017
35
7.2.6 Setting EDS current
Set the maximum locating current.
EDS441: 1-5 mA
EDS440: 10-50 mA
For further information, refer to
“Current” on page 53
.
10>
Chia sẻ với bạn bè của bạn: