BLUE SCOPE PHU MY 14MWP-đã chuyển đổi

RIAL



PLegends:VGlobHor sHorizontayl global irrasdiation
t TGlobEff REffective GloIbal, cAorr. for IAM anLd shadings

DiffHor Horizontal diffuse irradiation T_Amb T amb.
GlobInc Global incident in coll. plane
EArray Effective energy at the output of the array E_Grid Energy injected into grid
PR Performance Ratio

PVSYST V6.88




19/05/22

Page 4/5

Grid-Connected System: Special graphs
Project : BLUESCOPE
Simulation variant : BLUESCOPE 14MWP MÁI ĐÔNG_TÂY

Main system parameters System type No 3D scene defined, no shadings
PV Field Orientation 2 orientations Tilt/Azimuth = 10°/-90° and 10°/90°
PV modules Model LR4-72 HPH 435 M Pnom 435 Wp
PV Array Nb. of modules 32184 Pnom total 14000 kWp

InvePrter VsysModtel PVS-1T00-TL RIPnomA100 kW aLc Inverter pack Nb. of units 112.0 Pnom total 11200 kW ac


User's needs Unlimited load (grid)



Daily Input/Output diagram

100000
Values from 01/01 to 31/12


80000
PV60000 syst TRIAL


40000
20000
0
0 1 2 3 4 5 6 7 8
Global incident in coll. plane [kWh/m².day]
PVsySystemsOutputt PowerTDistribuRtion IAL
500000
Values from 01/01 to 31/12


400000
300000
PV200000 syst TRIAL
100000
0
0 2000 4000 6000 8000 10000 12000
Power injected into grid [kW]


Energy injected into grid [kWh / Bin]

Energy injected into grid [kWh/day]



PVSYST V6.88




19/05/22

Page 5/5

Grid-Connected System: Loss diagram
Project : BLUESCOPE
Simulation variant : BLUESCOPE 14MWP MÁI ĐÔNG_TÂY

Main system parameters System type No 3D scene defined, no shadings
PV Field Orientation 2 orientations Tilt/Azimuth = 10°/-90° and 10°/90°
PV modules Model LR4-72 HPH 435 M Pnom 435 Wp
PV Array Nb. of modules 32184 Pnom total 14000 kWp

InvePrter VsysModtel PVS-1T00-TL RIPnomA100 kW aLc Inverter pack Nb. of units 112.0 Pnom total 11200 kW ac


User's needs Unlimited load (grid)



Loss diagram over the whole year


1791 kWh/m² Horizontal global irradiation

-0.76% Global incident in coll. plane


-0.04% Global incident below threshold
-2.56% IAM factor on global
-2.00% Soiling loss factor
PV1697 kWh/sm² * 71609 my² coll. stEffective Tirradiation Ron collectors IAL
efficiency at STC = 19.57% PV conversion
23780 MWh Array nominal energy (at STC effic.)
-0.15% PV loss due to irradiance level
-7.58% PV loss due to temperature

-2.00% Module quality loss


-1.10% Mismatch loss, modules and strings
-0.62% Ohmic wiring loss
21137 MWh Array virtual energy at MPP

-1.89% Inverter Loss during operation (efficiency)


PVsy-0s.10% tInverter LoTss over nomRinal inv. powerIAL
0.00% Inverter Loss due to max. input current
0.00% Inverter Loss over nominal inv. voltage 0.00% Inverter Loss due to power threshold 0.00% Inverter Loss due to voltage threshold
20715 MWh Available Energy at Inverter Output

-0.99% System unavailability


20510 MWh Energy injected into grid
PVsyst TRIAL