Vlf sine 1 Hz – Universal voltage source for test- ing and diagnostics of medium-voltage cables



tải về 225.12 Kb.
Chế độ xem pdf
trang7/9
Chuyển đổi dữ liệu05.05.2023
Kích225.12 Kb.
#54635
1   2   3   4   5   6   7   8   9
PA VLF sine 01Hz Universal voltage source for testing and diagnostics of medium-voltage cables 210314 EN
9 2020 gt thi nghiem dien 1 tc ktd19md38 7318
STDTD 
0.5U
0
 (kV) U
0
 (kV) 1.5U
0
 (kV) 
3.5 
6.5 
10 
L1 
0.068 
0.036 
0.060 
L2 
4.453 
2.313 
9.343 
L3 
0.063 
0.004 
0.050 
Table 2: Measured values for Figure 4: 
Fig. 5: Drying effect of moist joints during a MWT 
The tan delta standard deviation on con-
ductor 2, identified in Fig. 4, strengthens 
the suspicion of a moist joint, as the PD 
test cannot detect any PD activity (too 
much moisture). The MWT, i.e. the combi-
nation of cable testing and tan delta meas-
urement over 15 minutes, conveyed that 
the joint had dried up and that the tan delta 
had clearly dropped (Fig. 5). This rein-
forced the suspicion of wet joints. 
6. Effects of the voltage source – Ex-
ample E-Werk Mittelbaden 
About ten years ago, the Elektrizitätswerk 
Mittelbaden Netzbetriebsgesellschaft mbH 
(short E-Werk Mittelbaden) carried out a 
comparison of VLF 0.1 Hz sine and a 50 
Hz method for the PD test based on over 
40 cable routes. As the 50 Hz method pro-
duced too many highly varying evaluations 
and especially more negative prognosis at 
the time, which until today were not con-
sidered as losses, the company decided on 
the VLF 0.1 Hz sine method. In the mean-
while, the VLF measurement with sine volt-
age has been established in hundreds of 
tests. This was evident in the diagnostic 
measurements, performed on 240 kilome-
tres with 500 partial routes in the 20 kV 
network of the 
E-Werk Mittelbaden, on paper pulp insu-
lated and mixed cable routes. 
At the E-Werk Mittelbaden, such cable 
routes with a VLF sine 0.1 Hz have been 
diagnosed by means of PD, and since 
about seven years, also by means of the 
tan delta measurement. According to Wer-
ner Brucker, Director of network opera-
tions, both these diagnostic procedures 
produced a good overall view of the age 
and condition of the network. Partial routes 
classified as dangerous will be replaced 
soon. The isolation of defective partial sec-
tions resulted in huge savings, as the entire 
cable run didn’t have to be replaced. 
In practice, the VLF measurement has 
proven to be suitable during the commis-
sioning tests of new or modified cable sys-
tems for locating faults precisely, and in 
future for detecting faults in the accessories 
with a simultaneous PD test so that the 
work involved for troubleshooting, such as 
installation faults, or during maintenance, 
e.g. excavation work, can be kept to the 
minimum. 
Brucker emphasises the weight and suita-
bility for daily use as an essential ad-
vantage of the VLF sine voltage source. 
The 0.1 Hz technology can be transported 
and operated by any employee, which 
would not have been possible with a 50 Hz 
system. 
The use of a test car with two persons is 
required very rarely, as the portable meas-
urement and testing device is enough for 
most cable lengths. A test car would be 
necessary only during the seventh meas-
urement or so. 
E-Werk Mittelbaden saw a clear cost ad-
vantage by applying the VLF 0.1 Hz tech-
nology: measurements could be easily per-
formed by a single employee in a short 
time. Due to the short connection time and 
test duration as well as the need for fewer 
people, several cable routes can easily be 
tested per year. Routes identified as critical 
during the measurements or partial sec-
tions will be scheduled for repair or re-
placement. Maintenance budgets can thus 
be deployed specifically. With the 
knowledge of weak points in the network 
and the condition-based maintenance, in 
spite of the growing cable stock, running 
the medium-voltage network with a low 
failure rate and in a cost-optimised manner 
has been successful. 
The maintenance plan at the E-Werk Mit-
telbaden is approx. EUR 4 million, of which 


Page 8 of 9 
EUR 2.5 million are relevant for the distri-
bution network. The costs for cable diag-
nostics at present are € 90,000/year. 
From the comparative tests conducted be-
fore procuring the VLF equipment, Brucker 
knows that there were distinct differences 
between VLF 0.1 Hz sine and 50 Hz meas-
urements for his tests. 
In practice, a changeover seemed no long-
er relevant, as the E-Werk Mittelbaden be-
came very familiar with the VLF 0.1 Hz 
measurements and its interpretation, and is 
able to use measured values with high reli-
ability for classifying cable routes. Even the 
prognosis whether a cable route is in dan-
ger in the short or medium term is possible 
with relative accuracy due to the wealth of 
experience, thus making it easier to priori-
tise maintenance measures accordingly. 