Isometer® iso685-d-p iso685W-d-p iso685-s-p iso685w-s-p insulation Monitoring Device with integrated locating current injector for it ac systems with galvanically connected rectifiers and inverters and for it dc systems



tải về 5.18 Mb.
Chế độ xem pdf
trang74/75
Chuyển đổi dữ liệu22.08.2023
Kích5.18 Mb.
#55079
1   ...   67   68   69   70   71   72   73   74   75
iso685-D-P D00170 M XXEN

Suitable system components
* Option W: Increased shock and vibration resistance 3K5, 3M7; -40…+70 °C
** 
SKMP = midscale point
Description
Type
Art. No.
Suitable measuring instruments
SKMP
**
: 28 kΩ,120 kΩ
Current values: 0…400 µA, 0…20 mA
(
for more information, click here
)
7204-1421
B986763
9604-1421
B986764
9620-1421
B986841
Display for front panel mounting
FP200
B91067904
FP200W
B91067904W
iso685-S-P
(only in combination with FP200)
Supply voltage:
AC 24…240 V; 50…400 Hz
DC 24…240 V
B91067130
iso685W-S-P*
(only in combination with FP200)
Supply voltage:
AC 24…240 V; 50…400 Hz
DC 24…240 V
B91067130W


iso685-D-P_D00170_03_M_XXEN/07.2017
88
19. Glossary
• BB bus
The BB bus is an interface which enables Bender devices to communicate with each other (Bender-internal device bus). 
The BB bus can be used with an ISOMETER® and one or more EDS44…-S.
• BCOM
Protocol for communication between Bender devices via an IP-based network.
• BS bus
The Bender sensor bus is an interface which enables Bender devices to communicate with each other (RS-485 interface).
• DHCP
Dynamic Host Configuration Protocol. It is used to assign the network configuration to Clients via a server.
• EDS
Insulation fault locator for fault location in an IT system.
• EDS button
The shortcut button "EDS" manually starts the insulation fault location, which runs continuously until the button is pressed again, which stops the 
process immediately.
(refer also to 
“Display elements and device buttons” on page 19
).
• EDS mode
The insulation fault location can be carried out in three different modes. Depending on the mode, the insulation fault location starts and stops due 
to different conditions (see also 
“Mode” on page 54
).
• ISOnet
Only one ISOMETER® may exist in an isolated system. If several networks monitored by an ISOMETER® are coupled, this function ensures via an 
Ethernet connection that only one ISOMETER® is actively measuring.
• Modbus TCP
Modbus is an international widely spread protocol for data transfer.
• PGH
PGH stands for locating current injector. The locating current injector generates a periodic locating current for insulation fault location. This locat-
ing current is detected by the measuring current transformers connected to the EDS and evaluated by the EDS.
• "PGH ON" LED
The "PGH ON" LED flashes during insulation fault location. It indicates that the locating current for the insulation fault location is generated.
• System (BCOM)
The system is the entire installation that is visible for the customer and defined by the customer. The BCOM communication takes place within this 
system. Naturally, different systems can exist independently in one network.
• Subsystem (BCOM)
The subsystem structures parts of the system as units defined by the customer, e.g. all PQ devices. A typical subsystem are also "non BCOM-capa-
ble" devices that are hidden behind a proxy.
• Web server
A web server presents the device functions graphically. The web server can be used for reading out measured values and for parameter setting.