iso685-D-P D00170 M XXEN

4.3 Connections and panel
A1/+, A2/-
Connection to the power supply voltage U
s
L1/+
Connector for the IT system to be monitored
L2 
Connector for the IT system to be monitored
L3/-
Connector for the IT system to be monitored
KE, E
Connection to PE
Top
PGH ON
ON
Display
RESET
DATA
LEDs: PGH ON, SERVICE, 
ALARM 1, ALARM 2
MENU
ESC
TEST
INFO
OK
X3
EDS
iso685-D-P
PGH ON
REMOTE
X4
X3
Optional expansion module for Bender devices (e. g. BB bus)
X4
REMOTE interface to connect to the FP200
iso685-S-P
Back
Front
ETH
X1
Multifunctional I/O interface (refer to 
page 24
)
ETH
Ethernet interface
R
Switchable terminating resistor for termination 
of the RS-485 interface
11 12 14
Connector for alarm relay 1
21 22 24
Connector for alarm relay 2
Bottom


Device overview
Device overview
iso685-D-P_D00170_03_M_XXEN/07.2017
19
4.4 Display elements and device buttons
Display elements
1
ON
The LED "ON" lights when the device is turned on.
The LED "ON" flashes during ISOnet operation if the device is active in the 
ISOnet interconnection.
2
The device display shows information regarding the device and the meas-
urements. 
Other information is available in the chapter
“Display” from page 37
.
3
PGH ON
The LED "PGH ON" flashes during insulation fault location. It indicates that 
the locating current for the insulation fault location is generated.
4
SERVICE
The LED "SERVICE" lights when there is either a device fault or a connection 
fault, or when the device is in maintenance mode. 
5
ALARM 1
The LED "ALARM 1" lights when the insulation resistance of the IT system 
falls below the set response value R
an1
.
6
ALARM 2
The LED "ALARM 2" lights when the insulation resistance of the IT system 
falls below the set response value R
an2
.
PGH ON