8.3.2. Manual Mode Excitation & Turns Ratio
In the main screen select ü
Manual
"Exci & TR" for Excitation and Turns Ratio
Press and hold the Start button.
Step 1 Degauss:
Press and hold the Surveillance Switch for
the complete measurement.
use Rotary Encoder to increase voltage.
Press the Push-Button or
Exci to start
Excitation.
Step 2 Excitation:
use Rotary Encoder to decrease voltage.
(Voltage can only decreased)
Values are stared automatically.
Press the Push-Button or
TR to start the
Turns Ratio.
90225-1.30 Instruction Manual CT-T1
Page 38 of 62
8.3.4. Manual Mode Turns Ratio
Select ü Manual
Select "TR" for Turns Ratio only
Press and hold the Start button.
Step 1 Select Ux / Ix:
Press and hold the Surveillance Switch for
the complete measurement.
use Rotary Encoder to increase voltage.
Press TR to measure TR.
Step 2 Turns Ratio:
Measure TR. Press Save to store TR.
Press Select
to select another voltage
(1. Step).
Press Stop to stop the measurement.
90225-1.30 Instruction Manual CT-T1
Page 40 of 62