4.2 Measurement Process
1. Configure the CT-T1 to measure the
example setup depicted in Figure 1. Turn
on the CT-T1 and you will be presented
with the tap configuration.
2. Press Info to see the "Rated Current"
screen. Enter the appropriate values based
on CT specifications.
3. The properties of the current transformer
to be tested can be entered in the
"Nameplate" screen.
4. If the CT under test is sensitive and
certain voltage or current values must not
be exceeded, these limits can be set in the
"Limits" tab.
Then press OK when you
enter the required information
90225-1.30 Instruction Manual CT-T1
Page 12 of 62
5. The grid can be used directly to select
the windings. However, in this case you
can also tap the X3
button to select the
corresponding windings. Finally press and
hold the Start button to start the test.
6. The Degauss process starts. In this step
the voltage is increased until the slope is
flat enough. Please note the red area on
the top of the graph that would disappears
when the Surveillance Switch is pressed.
7. During the Excitation process, the
voltage is slowly decreased until the slope
is steep enough and the graph is extended.
Please keep holding down the Surveillance
Switch as long as the voltage is above 50V.
8. The Turns ratio is measured at different
voltages below the detected Knee point.
Please keep holding down the Surveillance
Switch during this step as the voltage might
be increased above 50V depending on the
detected Knee point.
90225-1.30 Instruction Manual CT-T1
Page 13 of 62
13. The second winding can be highlighted
using the < and > buttons on the top.
14. After pressing Back ,the available
results are marked with bule flags in the
Main screen.