Setting System Variables
Section 5 Alarm and Event
62
3BSE035983-510
Setting Variables in System Variables Dialog Box
StandardEnableSource
If this choice is selected, the OPC Alarm and Event interface
supports standard
Enable/Disable by source. This means that all alarms in one object by source are
enabled or disabled at the same time.
If this choice is not selected, it is possible to enable or disable single alarms in one
object by source.
SendDisabledAE
If this
choice is selected, disabled alarms (conditions) are also sent to the OPC
Alarm and Event client on refresh.
If this choice is not selected, no disabled alarms (conditions) are sent to the OPC
Alarm and Event client on refresh.
All the other
system variables available, are presented in the
AE Settings dialog
box, (
Settings > AE Settings...). See
Alarm
and Event Settings
on page 24.
If you wish to disconnect the additional service from the OPC Server, thus not
sending disabled alarms while refresh then
set the variables
StandardEnableSource =
true and
SendDisabledAE =
false.
For more information about system variables, see the
OPC Server for AC 800M
Online Help.