Configuration revision: The revision number shall match the
subscriber’s configuration revision and shall be increased only by experts.
◦
DI for test mode: selection of digital inputs that can be used to put the
GCB to test mode. A digital input needs to be configured here. The test bit
follows the status of this set digital input.
◦
Test mode: select the checkbox to enable test mode.
◦
Application ID: update the value according to the subscriber’s
configuration.
NOTE: The rest of the parameters in this setting view are pre-configured
and shall only be changed by experts.
Figure 9 - GOOSE configuration
3. In Communication > IEC 61850 data map(x), select the In use checkbox for
logical nodes (LN) that contain the data to be published.
For example, if logical output 1 is published, select In use for LO01GGIO77.
Browse through all the IEC 61850 data map(x) views until you find the right
line.
4. GOOSE communication configuration
IEC 61850 configuration instructions
P3APS19001EN
17
Figure 10 - IEC 61850 data map(5)
4. In the Communication > GOOSE GCB1: data points > DSG1 Data
configuration setting view, define the following settings:
◦
In the Signal column, select the data to be published, for example Logic1.
◦
Chia sẻ với bạn bè của bạn: |